FLR

>80%

rowred

Heat recovery units

HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND INTEGRATED CONTROL

from 700 to 23.500 m³/h

Supporting structure in extruded aluminium profiles and curtain panels (42mm. thick) of sandwich type with special sealing gaskets; exterior finish RAL 9002; thermal acoustic mineral wool insulation class 0 and high density.
Filtering sections of F7 efficiency class with soft bags on the outside air circuit and M5 on exhaust air circuit, removable from the side.
Fan sections with single inlet backward-curved blades plug-fans directly coupled to EC Brushless electronic motors.
Dynamic air-to-air type recovery system consisting of high efficiency enthalpy rotor, Eurovent certified, produced in aluminium alloy with hygroscopic treatment, complete with purge sector and drive belt engine designed for free-cooling management in on/off mode.
Complete control panel with remote-display and microprocessor for temperature control at fixed air flow, based on the operation logics designed to maximize energy savings and environmental comfort, thanks to the modulation of air flow guaranteed by the inverter technology. The unit is designed for RS485 connection to supervision systems based on Modbus RTU protocol.

  • Pre and/or post-heating electrical coil

    SKE

    External water cooling/heating section

    CCS

    Water post-heating coil

    SKW

    3-way valve with actuator

    V33

    3 damper mixing chamber

    MS3

    Additional compact filter M6 class, on fresh air side

    FC6

    Bag filter F7 class, on return air side

    FT7

    Bag filter F8 class, on fresh air side (to be combined with FC6)

    FT8 

    Filters differential pressure gauge

    PSTD

    Differential pressure transducer

    DPS

    CO2 air quality sensor

    AQS

    Room hygrostat

    HAS

    Ductable hygrostat

    HCS

    External damper

    SKR

    On/off actuator with spring return for external damper

    SSE

    External hood with network

    CFA

    Flexible connection

    GAT

    Roof for outdoor installation

    TPR

FLR

 

14

20

26

50

92

144

205

Airflow

m³/h

1200

2100

2900

5700

9500

13500

16500

Rated static prevalence

Pa

250

250

250

250

250

250

250

Maximum static prevalence

Pa

466

458

578

548

868

767

1050

1 m sound pressure level at the outside
of the machine

dB(A)

43

48

43

47

52

50

53

Total max current absorption

A

4,58

11,7

11,7

7,60

15,8

20,5

31,9

Power supply

V-Ph-Hz

230-1-50

400-3+N-50

Efficiency (1)

%

80,6

80,4

80,6

80,6

80,6

75,1

76,7

Recovered cooling capacity (1)

kW

3,06

5,35

7,40

14,60

24,3

32,1

37,5

Supply temperature (1)

°C

27,2

27,2

27,2

27,2

27,2

27,5

27,7

Efficiency (2)

%

80,2

80,0

80,1

80,2

80,1

74,5

71,0

Recovered heating capacity (2)

kW

14,9

26,0

35,9

70,6

118,0

155,3

180,9

Supply temperature (2)

°C

15,7

15,6

15,6

15,7

15,6

13,8

12,7

CONFORMITY TO EU 1253/2014

 

 

 

 

 

 

 

 

Recovery efficiency (5)

%

80,3

80,1

80,3

80,3

80,3

75

71

Filter correction factor

W/m³/s

0

0

0

0

0

0

0

SFP int limit

W/m³/s

1549

1549

1478

1362

1299

1140

1020

Total internal air pressure drop (5)

Pa

600

700

680

680

700

580

615

Overall fan static efficiency (6)

%

54,6

52,6

58,6

59,4

61,7

62,6

60,6

SFP int

W/m³/s

1099

1331

1160

1145

1135

927

1015

Fans

 

 

 

 

 

 

 

 

Max current consumption

A

2 x 2,60

2 x 6,70

2 x 6,80

2 x 4,00

2 x 8,40

4 x 5,13

4 x 7,98

Max. total power absorbed

kW

2 x 0,50

2 x 1,35

2 x 1,35

2 x 2,50

2 x 5,20

4 x 3,30

4 x 5,20

2009/125/EC ErP Compliance

2015

2015

2015

2015

2015

2015

2015

Motor protection rating

 

IP54

IP54

IP54

IP54

IP54

IP54

IP54

Power supply

V-Ph-Hz

230-1-50

400-3-50

Electric SKE heating accessory (1)

 

 

 

 

 

 

 

 

Stages

 

1

1

1

1

1

1

1

Heating capacity

kW

6,00

10,0

14,0

28,0

48,0

64,0

80,0

Current consumption

A

8,66

14,4

20,2

40,4

69,3

92,4

115

∆T air side

°C

14,7

14,0

14,2

14,4

14,9

13,9

12

Pressure drop

Pa

25

25

25

25

25

25

20

Power supply

V-Ph-Hz

400-3-50

Electric SKE heating accessory (2)

 

 

 

 

 

 

 

 

Stages

 

1

1

1

1

1

1

1

Heating capacity

kW

3,00

5,00

7,00

14,0

24,0

32,0

40,0

Current consumption

A

4,33

7,22

10,1

20,2

34,6

46,2

57,7

∆T air side

°C

7,4

7,0

7,1

7,2

7,4

7,0

7,1

Pressure drop

Pa

17

17

17

17

17

17

15

Power supply

V-Ph-Hz

400-3-50

CCS accessory

 

 

Rows

 

4

4

4

4

4

4

4

Total cooling capacity (3)

kW

10

16,7

22,8

45,3

78,8

118,4

140,5

Sensible cooling capacity (3)

kW

5,6

9,5

13

25,4

44,1

65,1

78,7

Supply temperature (3)

°C

13,8

14,4

14,5

14,4

14

13,3

13,8

Water flow (3) (4)

m³/h

1,7

2,9

3,9

7,8

13,6

20,3

24,2

Water pressure drop (3) (4)

kPa

11

16

18

20

25

26

17

Heating capacity (4)

kW

9,9

16,8

22,9

44,9

76,1

111,2

139,7

Supply temperature (4)

°C

39,5

38,7

38,4

35,5

38,7

39,5

39,2

SKW

 

 

Heating capacity (7)

kW

8,0

12,5

16,9

34,0

56,6

86,1

99,7

Water flow rate (7)

l/h

1384

2152

2912

5841

9735

14818

17145

Water pressure drop (7)

kPa

33

23

17

39

26

27

23

Air pressure drop (7)

Pa

42

60

67

69

63

51

52

(1) Outdoor air 32°C 50% RH, ambient air 26°C 50% RH
(2) Outdoor air -10°C 90% RH, ambient air 22°C 50% RH
(3) Water in 7° out 12°C
(4) Water in 45° out 40°C
(5) At dry conditions : outside air temperature 5°C, room air temperature 25°C
(6) Including motor & speed controller efficiency
(7) air inlet condition 14°C; in/out water temperature 45°/40°C

The table lists the sound power values (SWL) in octave bands and totals; it also indicates the values of sound pressure level (SPL) at 1 m, 5 m and 10 m at supply, return and at the outside of the unit. All values refer to the operation of the ducted unit at FULL speed and at the nominal flow rate.

FLR

SWL [dB] octave band [Hz]

SWL

SPL Supply

SPL Return

SPL Outside

                     

1 m

5 m

10 m

1 m

5 m

10 m

1 m

5 m

10 m

 

63

125

250

500

1000

2000

4000

8000

dB

dB(A)

dB(A)

dB(A)

dB(A)

dB(A)

dB(A)

dB(A)

dB(A)

dB(A)

dB(A)

14

43,0

50,0

70,0

66,0

66,0

69,0

66,0

59,0

75

74

61

49

43

55

45

39

43

33

27

20

55,0

60,0

74,0

74,0

71,0

73,0

70,0

64,0

80

78

67

53

47

59

49

43

48

38

32

26

50,0

56,0

71,0

70,0

67,0

69,0

66,0

60,0

76

74

63

49

43

54

45

39

43

34

28

50

46,0

54,0

75,0

76,0

74,0

74,0

71,0

70,0

82

80

69

55

49

58

49

44

47

38

33

92

50,0

58,0

80,0

78,0

80,0

78,0

75,0

83,0

87

86

75

61

55

64

55

50

52

43

38

144

47,0

56,0

81,0

76,0

78,0

78,0

75,0

75,0

86

84

73

59

53

61

53

48

50

42

37

205

53,0

61,0

84,0

81,0

83,0

81,0

78,0

86,0

91

89

78

64

58

65

57

53

53

45

41

FLR

 

14

20

26

50

92

144

205

A

mm

1690

1690

1690

1855

(1195+865)

(1195+865)

(1195+1030)

B

mm

700

865

1030

1360

1690

2020

2020

C

mm

1190

1190

1190

1520

1850

2180

2510

L

mm

620

785

950

1280

1610

1940

1940

H

mm

475

475

475

640

805

970

1135

Weight

kg

350

370

410

620

850

1120

1510

FLR

 

14

20

26

50

92

144

205

L1

mm

150

150

150

150

150

150

150

L2

mm

100

100

100

100

100

100

100

L3

mm

635

635

635

800

965

965

965

L4

mm

535

535

535

535

535

535

535

W1

mm

470

635

800

1130

1460

1790

1790

H1

mm

395

395

395

560

725

890

1055

FLR  

LC2

Manual selection of 3 speed

 

Automatic/manual selection of speed

 

EC fans management

 

Manual ON-OFF

 

Cool/change over valve management

CCS+V33

Heat valve management

SKW+V33

Cool/change over valve management

CCS

Heat pump management

CCS

Defrost recovery management

 

Water coil anti-freeze management

 

ON-OFF electric heater management

SKE

Filter pressure switch management

PSTD

Management of ventilation with CO2 probe

AQS

Management of ventilation with one or two pressure sensors

DPS

Free-cooling damper management

 

Management of mixing chamber

MS3

Management of mixing chamber with CO2 probe

AQS+MS3

Management of motorized dampers

SKR+SSE

Management of Boost by keyboard

 

Alarms management

 

Post ventilation

 

Weekly programming

 

Remote ON-OFF

 

Digital input for PIR occupancy

 

Digital input for fire alarm

 

Mode change (hot/cold) from digital input

 

Minimum thermal hot water temperature

 

Remote display with internal sensor

 

BMS Modbus RS485 protocol

 

Reference diagram

 
Click here

Contact form